Cabin 2 Furnace No Heat

Home Threads Equipment Cabin 2 Furnace No Heat

Tagged: ,

Viewing 1 reply thread
  • Author
    Posts
    • #3817
      Ben Cheek
      Keymaster

      Promise Woods Cabin 2 furnace was turned on at 3pm and produced no heat. Hosting called in at 9:20pm, still no heat. Fan worked.

      Check on unit showed 3 red blinks on Furnace indicator LED, meaning “Vent intake or termination problem”. Since this is first cycle since Spring check when doing final inspection for occupancy, the most likely cause is bird nest in one of the 2” induction lines.

      Unit was left off (cover removed) until lines can be checked.

      • This topic was modified 2 weeks ago by Dave Lewis.
    • #4068
      Dave Lewis
      Moderator

      +Blow out vent lines and Pressure lines. It is working now.

Viewing 1 reply thread